# NUT config: PowerWalker VFI ICR IoT
Network UPS Tools setup for a PowerWalker VFI ICR IoT UPS.
- **Master**: one host connected to the UPS via **USB** (`nutdrv_qx`), runs
`upsd` + `upsmon`, and serves status to the network on port `3493/tcp`.
- **Clients**: any other Linux hosts run `upsmon` as network slaves and shut
down gracefully when the master signals a power failure (FSD).
This avoids the undocumented Modbus TCP register map entirely. If you ever
want a pure-network (no USB) setup, you would need the Modbus register map
from PowerWalker support plus the `nutdrv_modbus` driver -- not used here.
## Layout
```
master/etc/nut/ config for the USB-connected host
client/etc/nut/ config for each network slave
install-master.sh deploy + permissions on the master
install-client.sh deploy on a client: sudo ./install-client.sh <MASTER_IP>
```
## Quick start
### Master (USB host)
```
sudo ./install-master.sh
# edit /etc/nut/upsd.users -> set monmaster / monslave passwords
# edit /etc/nut/upsmon.conf -> set the same monmaster password
sudo nutdrv_qx -a test -DD -x port=auto # confirm the driver reads values
sudo systemctl enable --now nut-server nut-monitor
upsc ups@localhost
```
If the test shows no/garbled values, retry with:
```
sudo nutdrv_qx -a test -DD -x port=auto -x protocol=voltronic -x novendor
```
and uncomment the matching lines in `master/etc/nut/ups.conf`.
### Each client
```
sudo ./install-client.sh <MASTER_IP>
# edit /etc/nut/upsmon.conf -> set the monslave password
sudo systemctl enable --now nut-monitor
upsc ups@<MASTER_IP>
```
## Notes
- Open `3493/tcp` on the master firewall for your client subnets.
- `runtimecal` in `ups.conf`: these UPS models may not report runtime;
NUT then estimates it. Format: `sec_at_full,full_pct,sec_at_half,half_pct`.
Adjust to your battery / EBM configuration.
- `upsd.users` holds plaintext credentials and is gitignored. Keep the real
file off the repo; distribute it out of band (or via your secrets tooling).
- To also cut UPS output power after the master shuts down, look into
`upsdrvctl shutdown` / the `POWERDOWNFLAG` mechanism -- intentionally left
out here to keep the first deployment simple.
+45
View File
@@ -0,0 +1,45 @@
#!/usr/bin/env bash
# install-client.sh -- deploy NUT network-slave config
# Usage: sudo ./install-client.sh <MASTER_IP>
# ASCII only.
set -euo pipefail
SRC="$(cd "$(dirname "$0")" && pwd)/client/etc/nut"
DST="/etc/nut"
if [ "$(id -u)" -ne 0 ]; then
echo "ERROR: run as root (sudo)." >&2
exit 1
fi
MASTER_IP="${1:-}"
if [ -z "$MASTER_IP" ]; then
echo "Usage: sudo $0 <MASTER_IP>" >&2
exit 1
fi
echo "== Installing NUT (if missing) =="
if command -v apt-get >/dev/null 2>&1; then
apt-get update && apt-get install -y nut
elif command -v dnf >/dev/null 2>&1; then
dnf install -y nut
else
echo "WARN: unknown package manager, install 'nut' manually." >&2
fi
echo "== Copying client config to ${DST} =="
install -d "$DST"
cp -v "$SRC/nut.conf" "$DST/nut.conf"
sed "s/MASTER_IP/${MASTER_IP}/" "$SRC/upsmon.conf" > "$DST/upsmon.conf"
chown root:nut "$DST/upsmon.conf" 2>/dev/null || true
chmod 640 "$DST/upsmon.conf"
echo
echo "NEXT STEPS (manual):"
echo " 1. Edit ${DST}/upsmon.conf -- replace CHANGE_ME_SLAVE with the master's monslave password."
echo " 2. Enable the monitor service:"
echo " systemctl enable --now nut-monitor"
echo " 3. Verify connectivity to the master:"
echo " upsc ups@${MASTER_IP}"
+52
View File
@@ -0,0 +1,52 @@
#!/usr/bin/env bash
# install-master.sh -- deploy NUT master config for PowerWalker VFI ICR IoT
# Run as root on the USB-connected host. ASCII only.
set -euo pipefail
SRC="$(cd "$(dirname "$0")" && pwd)/master/etc/nut"
DST="/etc/nut"
if [ "$(id -u)" -ne 0 ]; then
echo "ERROR: run as root (sudo)." >&2
exit 1
fi
echo "== Installing NUT (if missing) =="
if command -v apt-get >/dev/null 2>&1; then
apt-get update && apt-get install -y nut
elif command -v dnf >/dev/null 2>&1; then
dnf install -y nut
else
echo "WARN: unknown package manager, install 'nut' manually." >&2
fi
echo "== Copying config files to ${DST} =="
install -d "$DST"
cp -v "$SRC/ups.conf" "$DST/ups.conf"
cp -v "$SRC/nut.conf" "$DST/nut.conf"
cp -v "$SRC/upsd.conf" "$DST/upsd.conf"
cp -v "$SRC/upsmon.conf" "$DST/upsmon.conf"
if [ ! -f "$DST/upsd.users" ]; then
cp -v "$SRC/upsd.users.example" "$DST/upsd.users"
echo "NOTE: created upsd.users from example -- edit the passwords now."
else
echo "NOTE: upsd.users already exists, left untouched."
fi
echo "== Setting ownership and permissions =="
chown root:nut "$DST"/*.conf "$DST/upsd.users" 2>/dev/null || true
chmod 640 "$DST/upsd.users" "$DST/upsmon.conf"
echo
echo "NEXT STEPS (manual):"
echo " 1. Edit ${DST}/upsd.users and ${DST}/upsmon.conf -- replace CHANGE_ME_* passwords."
echo " 2. Plug in the UPS via USB and test the driver:"
echo " nutdrv_qx -a test -DD -x port=auto"
echo " (add -x protocol=voltronic -x novendor if values are missing)"
echo " 3. Enable services:"
echo " systemctl enable --now nut-server nut-monitor"
echo " 4. Verify:"
echo " upsc ups@localhost"
echo " 5. Open 3493/tcp in the firewall for your client subnets."
+16
View File
@@ -0,0 +1,16 @@
# /etc/nut/ups.conf -- MASTER (USB-connected host)
# PowerWalker VFI ICR IoT via nutdrv_qx over USB.
#
# Uncomment the protocol/novendor/runtimecal lines only if the bare
# config does not return clean values. See README for the test command.
[ups]
driver = nutdrv_qx
port = auto
desc = "PowerWalker VFI ICR IoT"
pollinterval = 5
# Fallbacks (enable if needed):
# protocol = voltronic
# novendor
# runtimecal = 600,100,1200,50