# NUT config: PowerWalker VFI ICR IoT
|
||||
|
||||
Network UPS Tools setup for a PowerWalker VFI ICR IoT UPS.
|
||||
|
||||
- **Master**: one host connected to the UPS via **USB** (`nutdrv_qx`), runs
|
||||
`upsd` + `upsmon`, and serves status to the network on port `3493/tcp`.
|
||||
- **Clients**: any other Linux hosts run `upsmon` as network slaves and shut
|
||||
down gracefully when the master signals a power failure (FSD).
|
||||
|
||||
This avoids the undocumented Modbus TCP register map entirely. If you ever
|
||||
want a pure-network (no USB) setup, you would need the Modbus register map
|
||||
from PowerWalker support plus the `nutdrv_modbus` driver -- not used here.
|
||||
|
||||
## Layout
|
||||
|
||||
```
|
||||
master/etc/nut/ config for the USB-connected host
|
||||
client/etc/nut/ config for each network slave
|
||||
install-master.sh deploy + permissions on the master
|
||||
install-client.sh deploy on a client: sudo ./install-client.sh <MASTER_IP>
|
||||
```
|
||||
|
||||
## Quick start
|
||||
|
||||
### Master (USB host)
|
||||
|
||||
```
|
||||
sudo ./install-master.sh
|
||||
# edit /etc/nut/upsd.users -> set monmaster / monslave passwords
|
||||
# edit /etc/nut/upsmon.conf -> set the same monmaster password
|
||||
sudo nutdrv_qx -a test -DD -x port=auto # confirm the driver reads values
|
||||
sudo systemctl enable --now nut-server nut-monitor
|
||||
upsc ups@localhost
|
||||
```
|
||||
|
||||
If the test shows no/garbled values, retry with:
|
||||
|
||||
```
|
||||
sudo nutdrv_qx -a test -DD -x port=auto -x protocol=voltronic -x novendor
|
||||
```
|
||||
|
||||
and uncomment the matching lines in `master/etc/nut/ups.conf`.
|
||||
|
||||
### Each client
|
||||
|
||||
```
|
||||
sudo ./install-client.sh <MASTER_IP>
|
||||
# edit /etc/nut/upsmon.conf -> set the monslave password
|
||||
sudo systemctl enable --now nut-monitor
|
||||
upsc ups@<MASTER_IP>
|
||||
```
|
||||
|
||||
## Notes
|
||||
|
||||
- Open `3493/tcp` on the master firewall for your client subnets.
|
||||
- `runtimecal` in `ups.conf`: these UPS models may not report runtime;
|
||||
NUT then estimates it. Format: `sec_at_full,full_pct,sec_at_half,half_pct`.
|
||||
Adjust to your battery / EBM configuration.
|
||||
- `upsd.users` holds plaintext credentials and is gitignored. Keep the real
|
||||
file off the repo; distribute it out of band (or via your secrets tooling).
|
||||
- To also cut UPS output power after the master shuts down, look into
|
||||
`upsdrvctl shutdown` / the `POWERDOWNFLAG` mechanism -- intentionally left
|
||||
out here to keep the first deployment simple.
|
||||